Voltage rating
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664A)
AC 250 V; DC 28 V
0.05...16 A
1 A, AC 250 V/DC 28 V
5,000 operations at 2 x I
N
-20...+60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
main circuit
to aux. circuit
aux. circuit 4-5 to 6-7
Insulation resistance
Interrupting capacity I
cn
Interrupting capacity
(UL 1077)
Test voltage
AC 3000 V
AC 1500 V
AC 840 V
> 100 M
(DC 500 V)
10 x I
N
I
N
0.05...4.5 A
5...7 A
8...15 A
16 A
operating area IP 40
terminal area IP 00
10 g (57-500 Hz)
±
0.76 mm (10-57 Hz),
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
40 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 25 g
U
N
AC 250 V
AC 250 V
AC 250 V
AC 250 V
200 A
1000 A
2000 A
3500 A
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Thermal Overcurrent Circuit Breakers 2-6200/2-6400-...
Single pole thermal circuit breakers with push-to-reset, tease-free,
trip-free, snap action mechanism (R type TO CBE to EN 60934; M-type
when fitted with manual release features/type 2-6200 only). Featuring
auxiliary contacts (1 x N/C; 1 x N/O) as standard. Options include
manual release (type 2-6200 only), an additional unprotected circuit tap
(-A3), a centre reset position in which all contacts are open (-ZR: type
2-6200-H only), and -KF housing particularly suited to high humidity
and other damp conditions. Approved to CBE standard EN 60934 (IEC
934).
Description
Technical data
2-6200-...
2-6400...
Typical applications
Motors, transformers, solenoids, controls for oil and gas boilers.
Accessories
For type 2-6400 with IG1 threadneck
X 200 799 02
Water splash cover/knurled nut assembly.
X 200 799 01
As above with the cover bonded to the nut for
extra retention.
X 200 798 01/02 as X 200 799 02 and 01 above but featuring a
slotted knurled ring for wrench front of panel
tightening.
X 210 739 01
Water splash cover/hex nut. The concertina design
is extended when the button trips to the OFF position.
For type 2-6400 with IG 2 threadneck
X 210 663 01
Water splash cover/knurled nut assembly.
X 201 296 01
Water splash cover/hex nut assembly -
without 'O'ring.
Separate hardware
Y 300 192 01
3/8" hex nut.
Y 300 284 02
3/8" knurled nut.
Y 300 116 02
12 mm hex nut.
Y 300 065 01
12 mm knurled nut.
Ordering information
Type No.
2-6200
2-6400
flange mounting, with auxiliary contacts
threadneck panel mounting, with auxiliary contacts*
Mounting (type 2-6400 only)
IG1
moulded threadneck 3/8-27UNS-2A
IG2
moulded threadneck M 12 x 1
Terminal design - main circuit
L10
solder terminals
P10
blade terminals A6.3-0.8 mm
Shunt terminal
(optional)
A3
shunt terminal same as main terminal (up to 7 A/
5 A max. load; up to 16 A/10 A max. load)
Manual release
(optional)
H
manual release facility (type 2-6200 only)
Intermediate position
(optional)
ZR
intermediate position (type 2-6200-H only)
Auxiliary contacts
(standard)
Si
N/O and N/C contacts, solder terminals
Special housing
(optional)
KF
for tropical and high
humidity condition
Current ratings
0.05 ... 16 A
2-6200 - - P10 - - - - Si - - 8 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.
*mounting hardware bulk shipped