125
Issue C
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Circuit breakers to be fitted
2210-S291-P9M2-410005
2210-S291-P9M2-410033
AC 250 V, DC 65 V
max. 25 A per position
max. 80 A for complete unit
AC 240 V/DC 65 V
max. 1 A per position
Rated impulse
withstand voltage
2.5 kV
self-extinguishing
Voltage rating
Load
Signalisation (N/C contact)
Insulation co-ordination
(IEC 664 and 664A)
Pollution
degree
2
Flame resistance
(IEC 695, part 2-2)
Terminal design
input (terminal A/B):
clamp-type terminal 2.5 to 25 mm
2
single and stranded conductor
output (terminal block
+ or N,
⊥
or U)
clamp-type terminal 0.5 to 2.5 mm
2
single and stranded conductor
Typical volume resistances in main circuit
input terminal A/B +(N)
to output terminal + (N)
input terminal A/B - (U)
to female contact 2 (k)
input terminal A/B - Sig
to female contact 12
output terminal - (U)
to female contact 1
output terminal -
to female contact 11
Mass X2210-K0404 E
< 1,5 x 10
-3
< 1,5 x 10
-3
< 2 x 10
-3
< 1,5 x 10
-3
< 2 x 10
-3
approx. 280 g
Technical data
E-T-A rails distribute electrical power in telecommunications, automation,
data and control systems. A compact version is available for 3 to 9
loads. Mounting brackets and cover are not included.
Live parts in terminals areas are protected against brush contact (VDE
106 part 100).
Telecommunications systems (surveillance systems); process control.
Description
Typical applications
Ordering information
Distribution rail X2210-K...
X2210-K...
Type No.
X2210
Module for circuit breaker type 2210-...
Version
K compact distribution rail
Identification number
A3 for 3 circuit breakers
04 for 4 circuit breakers
05 for 5 circuit breakers
06 for 6 circuit breakers
07 for 7 circuit breakers
08 for 8 circuit breakers
09 for 9 circuit breakers
Terminal block (intermediate element) (fitted)
00 without
01 1 x
02 2 x
03 3 x
04 4 x
05 5 x
06 6 x
07 7 x
08 8 x
09 9 x
E short version
X2210 -
K 04 04 E ordering example for 4 positions