Issue C
4
%
Germany (0 91 87) 10-0 - USA (847) 827 - 7600 - UK (01296) 420336 - www.etacbe.com
219
Voltage rating
Current rating range
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664A)
AC 250 V (50/60 Hz); DC 28 V
0.05...16 A
4,000 operations at 2 x I
N
-30...+60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
>100 M
(DC 500 V)
0.05...5 A 400 A
5.5...7.5 A
8...16 A
750 A
1000 A (in accordance with
VDE 0636/IEC 269)
Degree of protection
(IEC 529/DIN 40050)
Vibration
operating area IP 40
terminal area IP 00
5 g (57-500 Hz)
±
0.38 mm (10-57 Hz)
to IEC 68-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
type 433: approx. 55 g
type 434: approx. 50 g
Shock
Corrosion
Humidity
Mass
Industrial equipment, control systems, power supplies.
Single pole high performance versions of types 3300 and 3400 (section
2) thermal-magnetic circuit breakers with tease-free, trip-free, press-
to-reset, snap action mechanism (R-type TM CBE to EN 60934; M-type
with manual release -H). Available with fast acting and standard
magnetic tripping characteristics - types 433 and 434 - both with
threadneck panel mounting. Options include a separate shunt tap
terminal (-A3), and pull-to-trip manual release (-H).
Complies with CBE standard EN 60934 (IEC 934).
Description
433-... 434-...
Typical applications
Technical data
High Performance Thermal-Magnetic Circuit Breakers 433/434-...
X 201 296 01
Concertina style splash cover/hex nut assembly for
version with press-to-reset only (-IG2), without O-
ring.
As above, but translucent, with O-ring
Splash seal/knurled nut assembly, allowing full
visibility of the push button actuator, for version with
press-to-reset only (-IG2).
X 200 801 08
X 210 663 01
Accessories
Ordering information
Current
rating (A)
Internal resistance (
)
433-...
(fast acting) (standardl)
477
131
41
32
10.3
7.2
4.8
2.50
1.93
0.81
0.44
Current
rating (A)
Internal resistance (
)
433-...
(fast acting) (standard)
0.27
0.183
0.109
0.066
0.046
0.032
≤
0.02
≤
0.02
≤
0.02
≤
0.02
≤
0.02
434-...
434-...
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
447
131
39.6
19.3
10.4
7.1
4.3
2.5
1.67
0.60
0.38
2.5
3
4
5
6
7
8
10
12
15
16
0.24
0.19
0.090
0.061
0.041
0.034
≤
0.02
≤
0.02
≤
0.02
≤
0.02
≤
0.02
Standard current ratings and typical internal resistance values
Approvals
Authority
VDE, Demko
Voltage ratings
AC 250 V, DC 28 V
Current ratings
0.05...16 A
Type No.
433
434
fast magnetic trip
delayed trip
Mounting
IG2
moulded threadneck M12x1, protection class II, not with -H
leave blank for metal threadneck (required for -H)
Terminal design
P10
blade terminals 6.3-0.8
K20
screw terminals M3.5x5.5 (not with -A3)
Manual release
(optional)
H
manual release facility ((pull)
for M12x1 metal threadneck only.
Shunt terminal
(optional, not with -K20)
A3
up to IN = 7 A max. load 5 A
Current ratings
0.05... 16 A
433 - IG2 - P10 - - - 5 A
ordering example, without manual
release and with moulded threadneck
433 - - P10 - H - - 5 A ordering example, with manual
release and metal threadneck
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.