Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Issue C
Max. operating voltage U
B
DC 60 V
(U
see Technical description)
adjustable between 0.1 and 3.1 A
(switch and potentiometer)
typically 35 mA
Current rating I
N
Current consumption
(U
= DC 36 V, U
= “0”)
Residual ripple for all voltages max. 5 % (3 phase bridge)
Reverse polarity protection U
B
double pole relay
(terminal 1 - terminal 2)
Physical isolation
2-pole
- by manual circuit breaker release
- approx. 5 s after overload
disconnection
- approx. 15 s after fault indication (RED
LED)
- approx. 0.5 s after thermal response
Load circuit
Load output
NPN transistor, minus switching,
pulse-controlled (approx. 180 Hz)
DC 24 V/adjustable betw. 0.1 and 3.1 A
U
B
/R
total
for approx. 400 ms
Load rating
Switch-on current I
E
(with short-circuit limitation)
Hold current I
Short-circuit limitation
Short-circuit current I
K (rms)
(depending on U
and I
N
)
Wire break monitoring
Current measuring terminals 2 x 2 mm dia. (shunt 0.1
±
1 %)
Leakage current (U
= 0)
typically 1 mA
Free-wheeling circuitry
integral electronic control with quick
(see Technical description)
disconnection
Control circuit
Control
opto coupler in control input
Control voltage U
S
“0” = 0 ... 5 V
“1” = 8.5...35 V
Control current I
typically 5 mA
Switching frequency f
1 Hz
Control signal (U
S
= “1”)
YELLOW LED lights (I
flowing)
Protection
reverse polarity protection (diode)
overvoltage protection (varistor)
Status outputs
2 signal outputs
ON indication/function indication
- physically isolated by opto coupler
- transistor outputs, plus switching
- auxiliary voltage U
: DC 12...60 V
- max. 50 mA per output
- integral free-wheeling diode
- reverse polarity and overvoltage
protection
ON indication (terminal 8)
U
S
= “0”: output non-conductive
U
= “1”: output connecting plus
potential (term. 10) to term. 8
Function indication
fault: output non-conductive
(terminal 9)
no fault: output connecting plus
potential (term. 10) to term. 9
typically 60 % of the set current rating
approx. 3.5 x IN
typically 10...400 mA
in the ON and OFF condition (RED LED)
Technical data
(T
A
= 25
°
C, U
B
= DC 36 V)
Description
Typical applications
Circuits with inductive load such as
- solenoids
- magnetic brakes etc.
in large plants, e.g. rolling mills where a very high availability is
required.
Features
E-1071-603
The E-T-A Solid State Remote Power Controllers E-1071-603/607 are
electronic control modules suitable for inductive loads such as soleno-
ids, magnetic brakes etc.
They are used
G
for safe and quick switching of loads
G
for monitoring the electrical condition of the loads
G
for compensating different cable lengths
The load connected to the relay should be operated with a voltage higher
than its rated voltage (DC 24 V) because the load current is controlled
electronically (pulse-controlled characteristics). This is to ensure that in
industrial plants with different cable lengths (supply cables, load cables)
an increased inrush current can be applied to each load. During hold
duty the load current is reduced to a smaller value (approx. 60 % of the
current rating), thus reducing the operating temperature and extending
the life of the loads.
G
Designed for inductive loads (DC 24 V)
G
Individual adjustment to various load currents (I
= 0.1...3.1 A)
G
Significant reduction of power loss in the load by pulse-controlled
characteristics
G
Short-circuit proof (short-circuit limitation); physical
disconnection from supply after approx. 5 s
G
Inrush current monitoring
G
Physical isolation:
- opto coupler in the control circuit
- physical disconnection from supply
- opto coupler for status outputs
G
Reverse polarity and overvoltage protection in the control, load
and status circuits
G
Control current indication by YELLOW LED
G
O.K. indication by GREEN LED
G
Wire break indication by RED LED (load circuit)
G
Fault indication by RED LED (incorrect setting etc.)
G
Two status outputs for PLCs for function indication (function
signal, ON signal)
G
Temperature disconnection
G
Quick disconnection (do not connect free-wheeling diodes to the
load as the free-wheeling current is controlled electronically!)
Ordering information
Solid State Remote Power Controllers E-1071-603/607
Type No.
E-1071
SSRPC
Terminals
603
607
screw terminals
screw-less connectors to Wago licence
Voltage rating of load
DC 24 V
Current rating
0.1 ... 3.1 A
E-1071 - 603 - DC 24 V - 0.1 ... 3.1 A ordering example