69
Issue C
1
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Authority
VDE, Semko
(EN 60934)
Voltage ratings
AC 250 V, DC 28 V
DC 50 V
DC 50 V
AC 250 V, DC 28 V
AC 250 V, DC 50 V
Current ratings
0.1...20 A
0.1...20 A double pole
0.1...10 A single pole
0.1...20 A
0.1...20 A
BV, LRoS
UL, CSA
3120-F...
Thermal Overcurrent Circuit Breaker 3120-F...
Voltage rating
Current ratings
Typical life
AC 250 V; DC 50 V
0.1...20 A (up to 30 A to special order)
50,000 operations for I
N
≤
16 A double pole
30,000 operations for I
N
≤
16 A single pole,
10,000 operations for I
N
>16 A
-30...+60
°
C
Rated impulse
Pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Dielectric strength
(IEC 664 and 664A)
operating area
between poles (2 pole)
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
AC 1500 V
>100 M
(DC 500 V)
0.1...2 A
2.5...20 A
10 x I
250 A 2 pole, or
150 A 1 pole
Interrupting capacity
(UL 1077)
I
N
0.1... 2 A
2.5... 3 A
3.5... 8 A
9 ... 16 A
18... 20 A
0.1...20 A
operating area IP 40
terminal area IP 00
8 g (57-500 Hz),
±
0.61 mm (10-57 Hz)
to IEC 68-2-6, Test Fc
10 frequency cycles/axis
30 g (11 ms)
to IEC 68-2-27, Test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, Test Ka
240 hours at 95 % RH,
to IEC 68-2-3, Test Ca
approx. 33 g (double pole)
approx. 27 g (single pole)
U
N
AC 250 V
AC 250 V
AC 250 V
AC 250 V
AC 250 V
DC 50 V
2 pole
200 A
1000 A
2000 A
3500 A
5000 A
1000 A
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Technical data
Description
Switch/thermal circuit breaker (S-type TO CBE to EN 60934) with
standard isolator style two button operation. Single button press-to-
reset version also available. Both types can be supplied in single pole
configuration only, in double pole with single pole protection, and in
double pole with protection on both poles. Designed for snap-in panel
mounting. There is a choice of push button colour combinations and
neon illumination (filament bulb for low voltages) is optional.
Any one of the following additional function modules can be supplied
factory fitted to the rear of the switch/circuit breaker.
G
Under voltage release coil (for double pole versions only).
G
Magnetic trip coil for short circuit protection - see page 113.
G
Magnetic trip coil for remote relay trip.
G
Auxiliary contacts for status signalling.
G
Mechanical slide interlock.
Approved to CBE standard EN 60934 (IEC 934).
Approvals
Current
rating
(A)
Internal
resistance per
pole (
)
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.2
1.5
2
2.5
3
94
24
12
5.30
4.20
2.90
1.50
0.9
0.80
0.45
0.27
0.0785
0.0595
Current
rating
(A)
Internal
resistance per
pole (
)
0.0565
0.0435
0.0435
0.0325
0.0215
0.0165
0.0165
<0.02
<0.02
<0.02
<0.02
< 0.02
< 0.02
3.5
4
4.5
5
6
7
8
10
12
14
16
18
20
Standard current ratings and typical internal resistance values
Typical applications
Motors, transformers, solenoids, extra low voltage wiring systems,
office machines, electro-medical equipment, power supplies, commu-
nications systems, industrial controls.
Accessories
Y 303 068 01
Insulated cover, snap-fitted to the exposed areas of the
two incoming terminals (when terminal screws are not
specified) to provide brush contact protection.
Terminal adapter to convert screw terminals to push on
connections when factory fitted under voltage release
module is specified (two adapters required per unit).
Retaining clip for -F3 mounting frame for panel
thickness under 2 mm.
As above for panel thickness under 4 mm.
Blanking piece in -F3 size mounting frame.
Rear terminal shroud.
Water splash cover for use with -F2 size mounting frame.
Retaining clip for -F2 mounting frame.
Y 303 862 01
Y 303 675 01
Y 303 675 02
Y 303 885 31
Y 304 275 01
Y 306 001 01
Y 306 551 01