74
1
Issue C
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Description
Dimensions
Internal connection diagrams
A module suitable for all double pole versions of type 3120 to trip the
main switch/circuit breaker mechanism in the event of loss of voltage.
When the voltage is restored the rocker switch must be reset to
reconnect the load, thereby avoiding the safety hazards associated
with automatic re-starting of machinery.
Note:
Basic unit 3120-...-H7 or -G7 screw terminals necessary.
Ordering information
Machines such as power tools, industrial equipment and domestic
appliances where automatic restart after restoration of power could be
dangerous (EU Machinery Directive)
Typical applications
Voltage ratings
AC 100, 120 V, 230/240 V 50/60 Hz
DC 24 V
20 to 70 % U
(at a rated voltage of AC 100 V the
device may release at 70 V and
must release at 20 V)
t < 20 ms
> 85 % U
N
-30...+60
°
C
8 g (57-500 Hz)
±
0.61 mm (10-57 Hz)
to IEC 68-2-6, test Fc
10 frequency cycles/axis
30 g (11 ms)
to IEC 68-2-27, test Ea
48 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95% RH
to IEC 68-2-30, test Ca
approx. 53 g (complete assembly)
Release values
Release delay
Latch-in values
Ambient temperature
Vibration
Shock
Corrosion
Humidity
Mass
Technical data
X3120-U00
X3120-U01
X3120-U02
Authority
VDE (EN 60934)
UL, CSA
Voltage ratings
AC 100...240 V; DC 24 V
AC 100...240 V; DC 24 V
Undervoltage Release Module X3120-U...for circuit breaker 3120-F...
Approvals (complete circuit breaker/module assembly)
12(k)
12(k)
12(k)
line
12(i)
22(i)
22(k)
U
11
21
load
line
11
12(i)
22(i)
22(k)
U
21
load
line
line
11
12(i)
22(i)
22(k)
U
21
load
line
1 terminal
X3120-U01…
blade terminal
DIN 46244-A2.8-0.8
flat head screw M3.5x5-MS ISO1580
for mains connection
2 terminals
X3120-U02…
21
22
23.5
21
6.6
3
15
°
7
10.7
41
+0.1
Without terminal(s): X3120-U00…
Type No.
X3120
Module for type 3120
Function
U undervoltage release module
Terminal design
00 standard (without separate connections)
01 1 blade terminal 2.8x0.8
02 2 blade terminals 2.8x0.8
Voltage ratings
00
230/240 V AC 50/60 Hz
01
120 V AC 50/60 Hz
02
100 V AC 50/60 Hz
03
24 V DC
M module mounted to the circuit breaker
X3120 - U 00 00
M
ordering example