81
Issue C
1
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
Current rating range
Typical life
Ambient temperature
Insulation co-ordination Rated impulse
(IEC 664 and 664 A)
AC 250 V; DC 28 V
0.05...10 A
2,000 operations at 2 x I
N
-20...+60
°
C
Pollution
withstand voltage degree
2.5 kV
reinforced insulation in operating area
2
Dielectric strength
(IEC 664 and 664 A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
> 100 M
(DC 500 V)
0.05...2 A 10 x I
N
2.5... 6 A
7 ... 10 A
8 x I
N
6 x I
N
Interrupting capacity
(UL 1077)
I
N
0.05...4.5 A
5 A
operating area IP 40
U
N
AC 250 V
AC 250 V
200 A
1000 A
Degree of protection
(IEC 529/DIN 40050) terminal area IP 00
Vibration
10 g (57-500 Hz)
±
0.76 mm (10-57 Hz),
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
25 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 15 g
Shock
Corrosion
Humidity
Mass
Thermal Overcurrent Circuit Breaker 2-4100-...
Technical data
Description
Single pole thermal circuit breaker with push-to-reset, tease-free, trip-free,
snap action mechanism (R-type TO CBE to EN 60934). Options include an
additional unprotected circuit tap (-A3) and -KF housing particularly suited
to high humidity and other damp conditions. Designed for threadneck
panel mounting. Approved to CBE standard EN 60934 (IEC 934).
2-4100-...
Typical applications
Motors, transformers, solenoids, hand tools, appliances.
Accessories
X 200 799 02
Water splash cover/knurled nut assembly for type
2-4100.
As above with the cover bonded to the nut for extra
retention.
As X 200 799 02 and 01 above but featuring a
slotted knurled ring for wrench front of panel
tightening.
Water splash cover/hex nut assembly for type
2-4100. The concertina design is extended when
the button trips to the OFF position.
Water splash cover transparent, with hex nut,
without O ring.
X 200 799 01
X 200 798 01/02
X 210 739 01
X 201 296 03
Approvals
Authority
VDE (EN 60934)
CSA
UL
Semko (EN 60934)
-A3 versions are not UL approved
Voltage rating
AC 250 V; DC 28 V
AC 250 V
AC 250 V
AC 250 V; DC 28 V
Current rating
0.05...10 A
0.05...3,5A
0.05... 5 A
0.1...10 A
Ordering information
Standard current ratings and typical internal resistance values
Currrent
rating (A)
0.05
0.08
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
1.2
1.5
Internal
resistance (
)
322
125
101
25
11
6.3
4.1
2.8
2.1
1.6
0.97
0.66
0.45
Current
rating (A)
1.8
2
2.5
3
3.5
4
4.5
5
6
7
8
10
Internal
resistance (
)
0.34
0.29
0.18
0.14
0.1
0.08
0.069
0.053
< 0.05
< 0.05
< 0.05
< 0.05
Type No.
2-4100
threadneck panel mounting
Terminal design
L10
solder terminals
P10
blade terminals A6.3-0.8 mm
P50
blade terminals A4.8-0.8 mm
Shunt terminal
(optional)
A3
shunt terminal (3 A max. load)
Special housing
(optional)
KF
for tropical and high humidity conditions
Current ratings
0.05 ... 10 A
2-4100 - L10 -
-
- 5 A
ordering example
The exact part number required can be built up from the table of choices shown