131
Issue C
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
AC 250 V; 3 AC 433 V (50/60 Hz); DC 65 V
AC 277/480 V UL/CSA
0.1...32 A
(32 A resistive load only)
1 A, AC 240 V / DC 65 V
10,000 operations at 1xI
N
-30...+60
°
C (T 60)
Rated impulse
Pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Dielectric strength
(IEC 664 and 664A)
operating area
main/aux. circuit
pole/pole
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
AC 3000 V
AC 1500 V
> 100 M
(DC 500 V)
0.1...5 A 400 A; 6...32 A 800 A;
Curve T2 : 0.1...32 A 15xI
N
Curve M3: 0.1... 2 A 200 A AC
Interrupting capacity
(UL 1077)
I
N
0.1...16 A
20...32 A
AC 277 V /2000 A
3 AC 480 V /2000 A
DC 65 V / 2000 A
1 + 2 pole AC 277 V /5000 A
3 pole
3 AC 480 V /5000 A
1 + 2 pole DC 65 V /2000 A
operating area IP 30
terminal area IP 20
Curve F1:
3 g (57-500 Hz),
±
0.23 mm (10-57 Hz)
Curves M1, M3, T1, T2:
5 g (57-500 Hz),
±
0.38 mm (10-57 Hz)
to IEC 68-2-6, Test Fc
10 frequency cycles/axis
Curve F1: 25 g (11 ms), directions 1,2,3,4,5
10 g (11 ms), direction 6
Curves M1, M3, T1, T2:
25 g (11 ms), directions 1,2,3,4,5
20 g (11 ms), direction 6
to IEC 68-2-27, Test Ea
96 hours at 5 % salt mist
to IEC 68-2-11, Test Ka
240 hours at 95 % RH
to IEC 68-2-3, Test Ca
approx. 60 g per pole
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Thermal-Magnetic Circuit Breaker 2210-T2..
One, two and three pole thermal-magnetic circuit breakers with trip-
free, snap action mechanism and toggle actuation (S-type TM CBE to
EN 60934/IEC 934). Featuring a combi-foot design for both symmetric
and asymmetric rail mounting. Available with auxiliary contact (1 x N/
O or 1 x N/C) for status signalling. Two and three pole models are
internally linked to ensure that both/all poles trip in the event of an
overload on one pole, even if the actuator is held in the ON position. This
CBE can be supplied in current ratings to 32 A with a choice of
characteristic curves. All screw terminals are recessed for safety.
Approved to CBE standard EN 60934 (IEC 934).
Description
Ordering information
2210-T2..
single pole 3 pole
Technical data
Process control equipment, robotics, machine tool control,
communications systems, instrumentation.
Typical applications
Type No.
2210 single and multi pole thermal-magnetic circuit breaker
Mounting
T rail mounting
Actuator design
2 toggle
Number of poles
1 single pole protected
2 2 pole protected
3 3 pole protected
4 4 pole protected
5 2 pole, protected on one pole only
Accessories
0 without accessories
Terminal design
(main contacts)
K0 screw terminals
Characteristic curve
F1
fast acting: therm. 1.01-1.4xI
N
;
magn.2-4xI
N
DC (DC only)
M1
standard delay: therm. 1.01-1.4xI
N
;
magn. 6-12xI
N
AC, 7.8-15.6xI
N
DC
T1
delayed: therm. 1.01-1.4 I
N
; magn. 10-20xI
N
AC
T2
thermal only, 1.01-1.4xI
N
M3
standard delay, low resistance: therm. 1.4-1.8xI
N
;
magn. 6-12xI
N
AC, 7.8-15.6 x I
N
DC
Auxiliary contact design
H without intermediate position
Auxiliary contacts
0 without auxiliary contacts
1 with auxiliary contacts
2 auxiliary contacts on pole 1 only
(multi pole devices)
3 auxiliary contacts on pole 1 and 3
(
≥
3 pole devices)
Auxiliary contact function
2 N/O contact
3 N/C contact
Auxiliary contact - terminal design
1 screw terminals
Current ratings
0.1 ... 32 A
2210 - T 2 1 0 - K0 M1 - H 1 2 1 - 10 A ordering example