149
Issue C
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
Current ratings
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
AC 250 V, 50/60 Hz; DC 28 V
0.05...25 A
4000 operations at 2xI
N
-30...+60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V double insulation
>100 M
(DC 500 V)
0.05...0.8 A self-limiting
1...2 A 200 A
2.5...25 A 400 A
operating area IP 40
terminal area IP 00
5 g (57-500 Hz)
±
0.38 mm (10-57 Hz)
to IEC 68-2-6, test Fc
10 frequency cycles/axis
25 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 50 g
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Single pole thermal-magnetic circuit breaker with tease-free, trip-free,
press-to-reset, snap action mechanism and additional manual release
(M-type TM CBE to EN 60934). Designed for plug-in mounting with
E-T-A sockets 10 and 16. Complies with CBE standard EN 60934 (IEC
934).
Thermal-Magnetic Overcurrent Circuit Breaker 3200
Description
3200-...
Technical data
Current
rating (A)
0.05
0.1
0.2
0.3
0.4
0.5
0.6
0.8
1
1.5
2
2.5
3
Internal
resistance (
)
534
149
56
24.2
13.6
8.1
5.25
3.55
2.02
0.90
0.51
0.36
0.23
Current
rating (A)
4
5
6
7
8
10
12
14
15
16
18
20
25
Internal
resistance (
)
0.141
0.107
0.060
0.049
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Standard current ratings and typical internal resistances
Control equipment, extra-low voltage wiring systems and components.
Typical applications
Accessories
10R-K10
Modular snap-together surface mounted sockets, each
accommodating two plug-in circuit breakers. With screw
terminals.
As above but with push-on terminals.
As above but with a combination of screw and push-on
terminals.
Two-way brass connecting/bus bar links for type 10
sockets.
Four-way brass connecting/bus bar links for type 10
sockets.
Single socket for symmetric EN rail mounting.
Blanking plug with insulated pins, for sockets
10, 20, 40, 60.
50-way 1.5mm
2
cable links with pre-fitted connection
lugs for type 10F-K10/-A10 sockets.
As above but with 2.5mm
2
cable links.
100-way 1.5mm
2
cable links with pre-fitted push-on
connectors for type 10F-P10 sockets.
As above but with 2.5mm
2
cable links.
10R-P10
10R-A10
Y 301 166 02
Y 301 166 01
16
Y 301 477 01
X 210 589 01
X 210 589 02
X 210 588 01
X 210 588 02
Ordering information
Type No.
3200
plug-in
Current ratings
0.05...25 A
3200 - 5 A ordering example
Authority
VDE
CSA
LRoS
Voltage ratings
AC 250 V, DC 28 V
AC 250 V, DC 28 V
AC 250 V, DC 28 V
Current ratings
0.05...25 A
0.05...15 A
0.3 ...25 A
Approvals