Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
E-T-A rails distribute electrical power in telecommunications, automation,
data and control systems. They have been designed to the BW7R
design requirement of the telecommunications industry. Mounting
brackets and cover are not included.
Live parts in terminal areas are protected against brush contact (VDE
106 part 100).
Description
Ordering information
Distribution rail X2210-K01.../K02.../K03...
Telecommunications systems of the BW7R design; process control,
measuring and control systems
Typical applications
Circuit breakers to be fitted
2210-S291-P9M2-410005
2210-S291-P9M2-410033
AC 250 V, DC 65 V
max. 25 A per position
max. 80 A for complete unit
AC 240 V/DC 65 V
max. 1 A per position
Rated impulse
withstand voltage
2.5 kV
self-extinguishing
Voltage rating
Load
Signalisation (N/C contact)
Insulation co-ordination
(IEC 664 asnd 664A)
Pollution
degree
2
Flame resistance
(IEC 695, part 2-2)
Terminal design
input (terminal A/B):
clamp-type terminal 2.5 to 25 mm
2
single and stranded conductor
output (terminal block
+ or N,
⊥
or U)
clamp-type terminal 0.5 to 2.5 mm
2
single and stranded conductor
Typical volume resistances in main circuit
input terminal A/B +(N)
to output terminal + (N)
input terminal A/B - (U)
to female contact 2 (k)
input terminal A/B - Sig
to female contact 12
output terminal - (U)
to female contact 1
output terminal -
to female contact 11
Mass X2210-K0116 B
< 1,5 x 10
-3
< 1,5 x 10
-3
< 2 x 10
-3
< 1,5 x 10
-3
< 2 x 10
-3
approx. 1140 g
Technical data
X2210-K01.../K02.../K03...
Type No.
X2210
Module for circuit breaker type 2210-...
Version
K distribution rail
Identification number
01 standard
02 distribution rail for remote supply
03 distribution rail, separate rails (2x8 outputs)
Terminal block (intermediate element) (fitted)
00 without
01 1 x
02 2 x
03 3 x
04 4 x
05 5 x
06 6 x
07 7 x
08 8 x
09 9 x
10 10 x
11 11 x
12 12 x
13 13 x
14 14 x
15 15 x
16 16 x
Accessories (fitted)
B insulating sleeving 2, cover 1
C insulating sleeving 2, cover 0
D insulating sleeving 0, cover 1
F insulating sleeving 1, cover 2, for remote supply
X2210 -