Thermal-Magnetic Circuit Breaker 2215-F1...
Typical time/current characteristics
N.B.
*Magnetic tripping currents are increased by 30% on DC supplies.
-F1
0.05...6 A
DC
-F1
8...10 A
DC
-M1
0.05...6 A
AC*
-M1
8...10 A
AC*
-T1
0.05...6 A
AC*
-T1
8...10 A
AC*
T
1
2
4
6 8 10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
6080 100
1
2
4
6 8 10
20
40
T
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
T
1
2
4
6 8 10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
T
1
2
4
6 8 10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
T
1
2
4
6 8 10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
T
1
2
4
6 8 10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
60 80100
+23
°
C
+60
°
C
-30
°
C
Time/current characteristics are calibrated at 23
°
C (see page 8). For operation
at other temperatures please apply the factors below to determine the circuit
breaker rating required.
Ambient temperature
°
C -30 -20 -10 0 +10 +23 +30 +40 +50 +60
Multiplication factor 0.76 0.79 0.83 0.88 0.93 1 1.04 1.11 1.19 1.29