141
Issue C
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
AC 250 V, 50/60 Hz; DC 48 V
(higher DC voltage to special order)
0.05...10 A
1 A, AC 250 V/DC 28 V resistive load
10,000 operations at 1xI
N
-30...+60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
pole/pole
main/aux. circuit
Insulation resistance
Interrupting capacity I
cn
Degree of protection
(IEC 529/DIN 40050)
Vibration
Test voltage
AC 3000 V
AC 1500 V
AC 1500 V
> 100 M
(DC 500 V)
600 A
operating area IP 30
terminal area IP 00
Curve F1:
6 g (57-500 Hz),
±
0.46 mm (10-57 Hz)
Curves M1, T1:
8 g (57-500 Hz),
±
0.61 mm (10-57 Hz)
to IEC 68-2-6, Test Fc
10 frequency cycles/axis
Curves F1, M1, T1:
30 g (11 ms), directions 1, 2, 3, 4, 5
Curve F1:
10 g (11 ms), direction 6
Curves M1, T1:
15 g (11 ms) direction 6
to IEC 68-2-27, Test Ea
96 hours at 5 % salt mist
to IEC 68-2-11, Test Ka
240 hours at 95 % RH
to IEC 68-2-3, Test Ca
approx. 50 g
Shock
Corrosion
Humidity
Mass
Thermal-Magnetic Circuit Breaker 2215-F1...
Miniaturised two pole thermal-magnetic circuit breakers with trip-free,
snap action mechanism and toggle actuation (S-type TM CBE to EN
60934). Fitted with panel mounting flange and push-on termination,
also suitable for mounting on Euro Cards. Available with auxiliary
contacts and a choice of fast, medium or long delay characteristics.
Complies with CBE standard EN 60934 (IEC 934).
Control equipment, communications systems, instrumentation.
Description
Typical applications
Ordering information
Technical data
2215-F1...
Current
ratings (A)
0.05
0.1
0.2
0,3
0.4
0.5
0.6
0.8
1
Internal resistance
per pole (
)
440
108
29.9
14.2
7.9
5.0
3.5
1.8
1.19
Current
ratings (A)
1.5
2
2.5
3
4
5
6
8
≤
0.02
10
≤
0.02
Internal resistance
per pole (
)
0.54
0.33
0.20
0.14
0.084
0.057
0.043
Standard current ratings and typical internal resistance values
Type No.
2215
double pole thermal-magnetic circuit breaker
Mounting
F1
flange mounting, with M3 mounting thread
Number of poles
2
2 pole protected
5
2 pole, protected on one pole only
Accessories
0
without
Terminal design (main contacts)
P1
blade terminals 6.3 x 0.8 mm,
without shunt terminal
Characteristic curve
F1
fast acting: 1.01-1.4xI
N
; magn. 2-4xI
N
DC
(DC only)
M1
standard delay: therm. 1.01-1.4xI
N
;
magn. 5-10xI
N
DC; magn. 3.5-8xI
N
AC
T1
delayed: therm. 1.01-1.4xI
N
;
magn. 8-16xI
N
DC; magn. 6-13xI
N
AC
Auxiliary contacts
S0 without auxiliary contacts
S1 with auxiliary contacts (change over)
S2 with auxiliary contact on pole 1 only
Auxiliary contact - terminal design
1
blade terminals 6.3x0.8
Current ratings
0.05...10 A
2215 -
F1
2
0 - P1
F1 - S1 1 - 0.5 A
ordering example