171
Issue C
3
%
Germany (0 91 87) 10-0 - USA (847) 827 - 7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
AC 240 V 50/60 Hz
DC 50 V
0.1...25 A
AC 125 V 3A; DC 30 V 2 A
10,000 operations at I
N
-40...+75
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in the operating area
Test voltage
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664A)
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
pole to pole
main to auxiliary circuit AC 1500 V
switching to trip circuit
Insulation resistance
Interrupting capacity I
cn
AC 3000 V
AC 1500 V
AC 1500 V
> 100 M
(DC 500 V)
1,000 A at AC 240 V
500 A at DC 50 V
operating area IP 40;
terminal area IP 00
single pole:
10 g (57-500 Hz)
±
0.76 mm (10-57)
double pole:
7 g (57-500 Hz)
±
0.54 mm (10-57)
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
50 g (6 ms)
to IEC 68-2-27, Test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, Test Ka
240 hours at 95 % RH,
to IEC 68-2-3, Test Ca
approx. 30 g per pole
(depending on version)
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Authority
UL/CSA
VDE
Voltage ratings
AC 240 V; DC 50 V
AC 240/ V; DC 50 V
Current ratings
0.1...25 A
0.1...25 A under test
Description
Typical applications
Approvals
Single and double pole magnetic and hydraulic-magnetic circuit breaker
with trip-free mechanism and toggle or rocker actuation. A choice of
fast magnetic only or hydraulically delayed switching characteristics (S
type MO or HM CBE to EN 60934/IEC 934) ensures suitability for a wide
range of applications. Low temperature sensitivity at rated load. Industry
standard dimensions and threadneck or snap in panel mounting.
Complies with CBE standard EN 60934 (IEC 934).
Power supplies, process control, switchgear and controlgear
Current rating (A)
0.1
1
2
3
5
10
15
20
25
Internal resistance (
) per pole
101
0.99
0.25
0.1
0.041
0.011
0.0057
0.0039
0.0028
Technical data
8330
Magnetic and Hydraulic-Magnetic Circuit Breaker 8330-...
Standard current ratings and typical internal resistance values