41
Issue C
1
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
AC 250 V; DC 28 V
(DC 50 V to special order)
0.05...16 A
0.05...4 A: 10,000 operations at 1 x I
N
5 ...16 A: 6,000 operations at 1 x I
N
-20...+60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Current ratings
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
> 100 M
(DC 500 V)
AC 250 V: 0.05...16 A 8 x I
N
DC 28 V:
0.05... 6 A 10 x I
N
7 ...10 A 200 A
12 ...16 A 300 A
I
N
U
N
0.05... 6 A
AC 250 V
7 ...16 A
AC 125 V
0.05...16 A
DC 50 V
operating area IP 40
terminal area IP 00
8 g (57-500 Hz)
±
0.61 mm (10-57 Hz),
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
30 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 12 g
Interrupting capacity
(UL 1077/EN60934 PC 1)
1000 A
1000 A
200 A
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Thermal Overcurrent Circuit Breaker 1110-...
Description
Single pole switch/thermal circuit breaker (M-type TO CBE to EN
60934) with tease-free, trip-free, snap action mechanism. Designed for
snap-in panel mounting utilising keyed round hole or industry standard
fuse-holder cut-out dimensions. Featuring an ergonomically styled two
colour actuator with indicator band clearly showing the tripped/OFF
position. Available with square or circular bezels.
Approved to CBE standard EN 60934 (IEC 934).
Technical data
1110-F1..
Authority
VDE
UL
Voltage ratings
AC 250 V; DC 28 V
AC 250 V
AC 125 V
DC 50 V
AC 250 V; DC 50 V
AC 250 V; DC 28 V
AC 250 V
Current ratings
0.05...16 A
0.05... 6 A
7 ... 16 A
0.05...16 A
0.05...16 A
0.5 ...16 A
0.05...10 A
CSA
LRoS, BV
Semko (EN 60934)
Approvals
Typical applications
Motors, transformers, solenoids, extra low voltage systems, household
and office machines, instrumentation, marine applications.
Accessories
Y 304 745 01
Y 305 602 01
Water splash cover for use with square bezels
Terminal shroud, for insulation or dust protection
Ordering information
Current
rating (A)
0.05
0.08
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1
1.2
1.5
1.8
Internal
resistance (
)
442
123
110
27.8
12.4
7.0
4.5
3.1
2.3
1.7
1.1
0.71
0.41
0.38
Current
rating (A)
2
2.5
3
3.5
4
5
6
7
8
10
12
15
16
Internal
resistance (
)
0.25
0.19
0.12
0.09
0.07
0.05
0.04
≤
0.02
≤
0.02
≤
0.02
≤
0.02
≤
0.02
≤
0.02
Standard current ratings and typical internal resistance values
Type No.
1110
snap in panel mounting
Mounting
F1 panel thickness 0.8...1.6 mm
F2 panel thickness 1.8...3 mm
F3 with location pin; panel thickness 0.8...1.6 mm
F4 with location pin, panel thickness 1.8...3 mm
Number of poles
1
1 pole protected
Actuator style
2
black push button/white indicator ring, standard
Other indicator ring colours are available to special order
Terminal design
P1 blade terminals A6.3-0.8
Characteristic curve
M1
medium delay
Current ratings
0.05...16 A
1110 - F1 1
2 - P1 M1 - 0.5 A
ordering example