179
Issue C
3
%
Germany (0 91 87) 10-0 - USA (847) 827 - 7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
3 AC 415 V; AC 240 V, 50/60 Hz; DC 80V
(higher DC ratings to special order)
0.02...30 A
6 A, AC 240 V/DC 28 V
1 A, DC 65 V; 0.5 A, DC 80 V
10,000 operations at 1xI
N
-40...+85
°
C
Rated impulse
Pollution
withstand voltage degree
2.5 kV
2
reinforced insulation in operating area
Current ratings
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664A)
Dielectric strength
(IEC 664 and 664A)
operating area
pole to pole
(2 and 3 pole)
AC 1500 V
main to auxiliary circuit
switching to trip circuit
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
AC 1500 V
AC 1500 V (version -X)
> 100 M
(DC 500 V)
1200 A at AC,
2000 A at DC
I
N
0.025...20 A
1 pole
AC 250 V/3500 A AC 250 V/3500 A
2 pole
AC 250 V/3500 A AC 250 V/5000 A
3 pole
3AC 250V/3500 A 3AC250V/5000 A
1 to 3 pole
DC 65 V/2000 A
operating area IP 40
terminal area IP 00
with toggle down: 10 g (57-2000Hz)
±
0.76mm (10-57 Hz) at 0.9xI
N
Directions 1, 2, 3, 4, 5:
10 g (57-2000 Hz) at 1xI
.
With curves F1, F2 in all planes:
10 g (57-2000 Hz)
±
0.76mm (10-57 Hz)
at 0.8xI
N
,
to IEC 68-2-6, test Fc
10 frequency cycles/axis
100 g (11 ms) at 1xI
N
, directions 1-5
100 g (11 ms) at 0.8xI
N
, direction 6.
With curves F1, F2:
100 g (11 ms) at 0.8xI
N
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 65 g per pole
Interrupting capacity
(UL 1077)
25...30 A
DC 65 V/2000 A
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-F...
Single and multipole magnetic circuit breakers with trip-free, snap-
action mechanism and toggle actuation. A choice of fast magnetic only
or hydraulically delayed switching characteristics (S-type MO or HM
CBE to EN 60934) ensures suitability for a wide range of applications.
Industry standard dimensions and panel mounting. Options include
auxiliary changeover contacts, or relay trip function.
Approved to CBE standard EN 60934 (IEC 934).
Description
Technical data
8340-F...
1 pole
2 pole
3 pole
X 211 117 01
X 211 118 01
X 211 119 01
Single pole splash cover with fixing plate.
Two pole splash cover with fixing plate.
Three pole splash cover with fixing plate.
Accessories
Control equipment, communications systems, transportation, power
supplies.
Typical applications
Current
rating (A)
0.02
0.05
0.1
0.25
0.5
0.75
1
2
2.5
3
5
6
8
10
12
15
16
20
25
30
Curves and internal resistance per pole (
)
F1
F2
1498
957
276
152
58
37
8.2
6.0
2.3
1.47
0.98
0.63
0.58
0.35
0.145
0.096
0.096
0.061
0.065
0.048
0.025
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
K1, M1, T1,
2669
452
100
15.5
3.9
1.65
0.95
0.26
0.15
0.10
0.042
0.029
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
K2, M2, T2
2457
376
94
14.7
3.2
1.56
0.90
0.20
0.15
0.10
0.040
0.028
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Standard current ratings and typical internal resistance values
Approvals
Authority
VDE (EN 60934)
UL, CSA
LRoS, BV
QPL (Sweden)
Voltage ratings
3 AC 415 V, AC 240 V, DC 80 V
3 AC 250 V, AC 250 V, DC 65 V
AC 250 V, DC 65 V
AC 240 V, DC 50 V
Current ratings
0.02...30 A
0.02...30 A
0.1 ...30 A
1 ...30 A