43
Issue C
1
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
Current ratings
Typical life
AC 240 V; DC 48 V (DC 50 V UL/CSA)
3.5...16 A
3.5...8 A 1000 operations at 2 x I
N
10...16 A 50 operations at 2 x I
N
-20...+60
°
C (T 60)
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
> 100 M
(DC 500 V)
3.5... 8 A 8 x I
N
10...16 A 120 A
I
N
3.5...16 A
3.5 ... 7A
8 ...16 A
operating area IP 40
terminal area IP 00
10 g (57-500 Hz)
±
0.76 mm (10-57 Hz),
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
25 g (11 ms)
to IEC 68-2-27, test Ea
96 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
240 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 10 g
Interrupting capacity
(UL 10777)
U
N
DC 50 V
AC 250 V
AC 250 V
200 A
1000 A
2000 A
Degree of protection
(IEC 529/DIN 40 050)
Vibration
Shock
Corrosion
Humidity
Mass
Authority
VDE
CSA
AC 250 V; DC 50 V
Semko
Kema (EN 60934)
Voltage ratings
AC 240 V; DC 28 V
AC 250 V, DC 50 V
3.5...16 A
AC 240 V
AC 240 V; DC 48 V
Current ratings
7 ...16 A
3.5...16 A
UL
7 ...16 A
3.5...16 A
3.5
4
5
6
7
8
0.06
0.04
0.03
0.02
< 0.02
< 0.02
Thermal Overcurrent Circuit Breaker 1140-...
Description
Miniaturised single pole thermal circuit breaker with push-to-reset
tease-free, trip-free, snap action mechanism (R-type TO CBE to EN
60934). Available in versions for panel mounting, snap-in or threadneck,
or as an integral type. For lower current ratings see types 104, 105, 106.
Approved to CBE standard EN 60934 (IEC 934).
Ordering information
Technical data
Standard current ratings and typical internal resistance values
Approvals
1140-E... 1140-F... 1140-G.1.
Motors, transformers, solenoids, hand-held machines and appliances.
Typical applications
X 201 285 01
Water splash cover/knurled nut assembly for type 1140-G.
Accessories
Current
rating (A)
Internal
resistance (
)
Current
rating (A)
10
12
13
15
16
Internal
resistance (
)
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
Type No.
1140
single pole thermal circuit breaker
Mounting
E2 integral mounting
F1 snap-in panel mounting
G0 threadneck panel mounting without mounting hardware
G1 threadneck panel mounting, with hex nut and knurled nut *
G2 threadneck panel mounting, for standard fuseholder cut-out *
G4 threadneck panel mounting with metal knurled nut*
Number of poles
1 1 pole protected
Actuator style
1
black push button
Terminal design
P1
blade terminals A6.3-0.8
Characteristic curve
M1
medium delay
Current ratings
3.5...16 A
1140 - F1 1 1 - P1 M1 - 10 A
ordering example
*mounting hardware bulk shipped