102
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Issue C
Dimensions
Internal connection diagram
Typical time/current characteristics
Installation drawing
for protection class II (IEC 730-1)
Type 201 0.05...7 A
AC
Type 201 8...16 A
AC
Type 201-WA 0.05...10 A
DC
Thermal-Magnetic Circuit Breaker 201/-WA
Magnetic tripping currents are decreased
by 20 % on AC supplies.
mounting area
operating area
(double insulation)
cable entry
cable entry
line 1
2
I >
… times rated current
+23
°
C
-30
°
C
+60
°
C
1
2
4
6 8
10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
6080100
T
1
2
4
6 8
10
20
40
10000
1000
100
10
1
0.1
0.01
0.001
6080100
T
T
1
2
4
6 8
10
20
40
… times rated current
10000
1000
100
10
1
0.1
0.01
0.001
6080100
Magnetic tripping currents are increased by 20 % on DC supplies.
Time/current characteristics are calibrated at 23
°
C (see page 8). For operation at
other temperatures please apply the factors below to determine the circuit
breaker rating required.
Ambient temperature
°
C
-20
Multiplication factor
0.76 0.84 0.92 1
-10
0
+23
+40
1.08 1.16 1.24
+50
+60
6
4
7
8.5
symmetrical rail EN 50022-35x7.5
current rating in A
Weidmüller
Type BS.1/2
SchT
PES
dekafix
T./WT
Wieland
Type 9003
Phoenix
Type DST6
4K-DST5
45
1
5
5
80
4
2
Phillips screw, size 2 to EN ISO 4757
O
O
slot for fitting labels from
12-14
conductor cross
section max.
0.5 - 10 mm
2
rigid conductor
0.5 - 6 mm
2
flexible conductor
tightening torque
max. 0.8 Nm
11.5
12.5