7
O
337
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Issue C
Description
Variants
Protection from
Lamp capacity
Voltage rating
Suitable for lighting systems with dimmers
Temperature range
Overload response
Typical trip times
overload
short-circuit
underload
Technical data
Dimensions
The Current Protector is connected in the
primary circuit before the low-voltage trans-
former (e.g. AC 230 V/12 V). Irregularities in
the secondary circuit, such as overloads or
short-circuits, will cause the Protector to
immediately disconnect the system. Under-
load (e.g. defective terminal connections)
also causes system disconnection. Error
indication by red LED. After removal of the
fault, the system can be reconnected by
operation of the storage push button on the
Protector or by operating the light switch.
E 1078-421 (up to 400 W)
E 1078-431 (up to 600 W)
short-circuit, overload, underload
60 - 300 W
100 - 400 W
300 - 600 W
AC 230 V
±
10 %/ 50 Hz
yes
0 ... +45
°
C
steplessly adjustable
200 ms to 2 s (depending on overload)
200 ms
3 s
see CPI cat. pages 139 - 140
Track-mountable housing
Protection of lighting systems
G
Available housing variants:
- track mountable on 35 mm EN rails
- housing for surface mounting in
transformers
Suitable for dimmer systems.
Detecting defective terminal connections
Line resistances, transformer
and lamp tolerances are
compensated for by the adjustment.
VDE approval in place
Option: load storage via light switch.
G
G
G
G
E 1078-422 (up to 400 W)
E 1078-432 (up to 600 W)
E 1078-482 (up to 600 W) load storage via
light switch
short-circuit, overload, underload
60 - 300 W
100 - 400 W
300 - 600 W
AC 230 V
±
10 % / 50 Hz
AC 120 V
±
10 % / 60 Hz
yes
0 ... +60
°
C
steplessly adjustable
200 ms to 2 s (depending on overload)
200 ms
3 s
see CPI cat. pages 141 - 142
Surface housing
Type No.
E 1078-421-/ 431-...
E 1078-422-/ 432-/ 482-...
Current Protectors
6
4
45
57
1.5
22.5
5
Speichern
Setting
1
Tr
2
N
3
L
4
Tr
1078-422 AC 230V 100-400VA
R
Fehler
Error
STROM-
WCHTER
PCURRENT
NV-STROMWCHTER
AC 230V 100-400VA
Error
Bei Fehlersignal zuerst
Storage
1/N 2/N 3/L 4/Tr
5
R
35
4
7
22
67
8319