105
Issue C
2
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Voltage rating
AC 250 V; 3 AC 433 V (50-60 Hz); DC 65 V
(higher voltages to special order)
0.1...25 A for curves M1, T1, T2
0.1...16 A for curves F1, M3
1 A, AC 240 V/DC 65 V
10,000 operations at 1xI
N
-30...+60
°
C (T 60)
Rated impulse
Pollution
withstand voltage degree
2,5 kV
2
reinforced insulation in operating area
Current rating range
Auxiliary circuit
Typical life
Ambient temperature
Insulation co-ordination
(IEC 664 and 664A)
Dielectric strength
(IEC 664 and 664A)
operating area
main/aux. circuit
aux. circuit 11-12/23-24 AC 1000 V
pole/pole
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 3000 V
AC 1500 V
AC 1500 V
> 100 M
(DC 500 V)
0.1...5 A 400 A; 6...25 A 800 A
Curve T2 : 0.1...25 A 15xI
N
Curve M3: 0.1... 2 A AC 200 A
Interrupting capacity
(UL 10771)
I
N
0.1...8 A 10...16 A 20A
AC 250 V
AC 125 V
1000 A
2000 A
2000 A
2000 A
3AC 250V
3AC 250V
2000 A
2000 A
operating area IP 30
terminal area IP 00
Curve F1:
3 g (57-500 Hz),
±
0.23 mm (10-57 Hz)
Curves M1, M3, T1, T2:
5 g (57-500 Hz),
±
0.38 mm (10-57 Hz)
to IEC 68-2-6, Test Fc
10 frequency cycles/axis
Curve F1: 25 g (11 ms), directions 1,2,3,4,5
10 g (11 ms), direction 6
Curves M1,M3, T1, T2:
25 g (11 ms), directions 1,2,3,4,5
20 g (11 ms), direction 6
to IEC 68-2-27, Test Ea
96 hours in 5 % salt mist
to IEC 68-2-11, Test Ka
240 hours at 95 % RH
to IEC 68-2-3, Test Ca
approx. 50 g per pole
0.1...20 A
DC 65 V
2000 A
2000 A
U
N
1 pole
2 pole
3 pole
AC 250 V
3500 A
3500 A
3AC 216V
3500 A
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
One, two and three pole thermal-magnetic circuit breakers with trip-free,
snap action mechanism and toggle actuation (S-type TM CBE to EN
60934/IEC 934). Designed for panel or plug-in mounting. Available with
auxiliary contacts (1 x N/O, 1 x N/C) for status signalling and fitted with an
unprotected shunt tap terminal as standard. Two and three pole models
are internally linked to ensure that both/all poles trip in the event of an
overload on one pole, even if the actuator is held in the ON position. A
choice of characteristic curves further extends the range of applications
possibilities for these CBEs. Approved to CBE standard EN 60934 (IEC
934).
Description
2210-S2...
Technical data
Thermal-Magnetic Circuit Breaker 2210-S..
Process control equipment, robotics, machine tool control, communications
systems, instrumentation. Special versions, e.g. for aggressive
environmental conditions and low voltages (5 V) on request.
Typical applications
Ordering information
Type No.
2210
single or multi pole thermal-magnetic circuit breaker
Mounting
S socket or panel mounting
Actuator design
2 toggle
Number of poles
1 1 pole protected
2 2 pole protected
3 3 pole protected
4 4 pole protected
5 2 pole, protected on one pole only
Panel mounting
0
without hardware
1
with M3 thread
2
with 6/32 thread
Terminal design
(main contacts)
P1 blade terminals 6.3-0.8
Characteristic curve
F1
fast acting: therm. 1.01-1.4xI
N
;
magn. 2-4xI
N
DC (DC only)
M1
standard delay: therm. 1.05-1.4xI
N
;
magn. 6-12xI
N
AC;7.8-15.6xI
N
DC
T1
delayed: therm. 1.01-1.4xI
N
; magn. 10-20xI
N
AC
T2
thermal only, 1.01-1.4xI
N
M3
standard delay, low resistance: therm.1.4-1.8xI
N
;
magn. 6-12xI
N
AC; 7.8-15.6xI
N
DC
Intermediate position
H without intermediate position (standard)
Z with intermediate position
Auxiliary contacts
0 without auxiliary contacts
1 with auxiliary contacts in all poles
2 with auxiliary contacts in pole 1
(only multi pole devices)
3 with auxiliary contacts in poles 1 and 3
(
≥
3 pole devices)
Auxiliary contact function
1 one each N/C and N/O (standard)
2 one N/O contact (23/24)
3 one N/C contact (11/12)
4 one N/O contact, closed in the
intermediate and ON position
Auxiliary contact - terminal design
1 same as main terminals
Current ratings
0.1...25 A
2210 - S 2 1 0 - P1 F1 - Z 1 1 1 - 10 A ordering example
Remote trip coil available to special order.