53
Issue C
1
%
Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.etacbe.com
Authority
SEV (EN 60934)
Voltage ratings
AC 240 V
DC 28 V
AC 125 V
DC 48 V
Current ratings
0.63... 4 A
0.63... 8 A
0.63...10 A
0.63... 8 A
CSA, UL
Voltage rating
Current rating range
Typical life
circuit 1-3
AC 240 V; DC 28 V (DC 48 UL/CSA)
0.63...10 A
30,000 operations for I
N
≤
6.3 A AC/DC
10,000 operations for I
N
> 6,3 A AC
3,000 operations for I
> 6,3 A DC
300 operations at 2 x I
N
-20 ... +60
°
C
Rated impulse
withstand voltage degree
2.5 kV
reinforced insulation in operating area
protection circuit 1-2
Ambient temperature
Insulation co-ordination
(IEC 664 and 664 A)
Pollution
2
Dielectric strength
(IEC 664 and 664A)
operating area
Insulation resistance
Interrupting capacity I
cn
Test voltage
AC 1500 V
> 100 M
(DC 500 V)
0.63...2.5 A 12 x I
N
3.15 ...10 A 8 x I
N
AC, max. 70 A
3.15 ...10 A 10 x I
DC
or to UL 1077 at AC 125/DC 48 V: 200 A
operating area IP 30
terminal area IP 00
8 g (57-500 Hz)
±
0.61 mm (10-57 Hz),
to IEC 68-2-6, Test Fc,
10 frequency cycles/axis
20 g (11 ms)
to IEC 68-2-27, test Ea
48 hours at 5 % salt mist,
to IEC 68-2-11, test Ka
96 hours at 95 % RH
to IEC 68-2-3, test Ca
approx. 9 g
Degree of protection
(IEC 529/DIN 40050)
Vibration
Shock
Corrosion
Humidity
Mass
Thermal Overcurrent Circuit Breaker 1410-F1...
Miniaturised single pole rocker switch/thermal circuit breaker combining
ON/OFF switching and extremely fast overload performance in a single
component (S-type TO CBE to EN 60934/IEC 934). Under overload
conditions an internal neon (filament bulb for low voltages) illuminates to
give a clear signal of the tripped status of the mechanism and thereby the
cause of power interruption, suffix -B. Alternatively the illumination can be
conventionally wired to indicate the ON status of the device, suffix -E.
Returning the rocker switch through the OFF position and back ON will
reset the mechanism and restore the supply. Largely temperature-insen-
sitive. Approved to CBE standard EN 60934 (IEC 934).
Description
Ordering information
Technical data
1410-F1..
Approvals
Typical applications
Motors, transformers, solenoids, PCBs, hand-held machines, ap-
pliances, instrumentation.
Standard current ratings and typical internal resistance values
Current
rating (A)
0.63
0.8
1
1.5
1.8
2
2.5
Internal
resistance (
)
1.05
1.0
< 1
< 1
< 0.8
< 0.8
< 0.12
Current
rating (A)
3.15
4
5
6.3
8
10
Internal
resistance (
)
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
< 0.1
Type No.
1410
snap-in panel mounting type
Mounting
F snap-in panel mounting
Size of frame
1 to fit mounting cut-out 28 x 12.7 mm
Number of poles
1 single pole, thermally protected
Accessories
0
without accessories
Terminal design
P1 blade terminals 2.8-0.8
Characteristic curve
F1
fast acting
Actuator style
W rocker, rounded profile
Actuator colour
14 red translucent
Actuator markings
Q I and 0
Trip/ON illumination (optional)
B illuminated when tripped
E illuminated when ON
Voltage range (optional)
2
20- 28V marked 24V 35mA
3
90-140V marked 115V <1mA
4
185-275V marked 230V <1mA
Current ratings
0.63...10 A
1410 - F 1 1 0 - P1 F1 - W 14 Q E 3 - 2 A ordering example
The exact part number required can be built up from the table of choices shown
above. Ordering references for optional features should be omitted if not required.