I-66
Digital Controller
E5CK
I
Characteristics
Note:
The indication accuracy of the K1, T, and N thermocouples at a temperature of
100
°
C or less is
±
2
°
C
±
1 digit maximum. The indication
accuracy of the U, L1, and L2 thermocouples at any temperature is
±
2
°
C
±
1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400
°
C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200
°
C or less is
±
3
°
C
±
1 digit maximum.
The indication accuracy of the W thermocouple at any temperature is (
±
0.3% of the indicated value or
±
3
°
C, whichever is greater)
±
1 digit
maximum.
The indication accuracy of the PL
II
thermocouple at any temperature is (
±
0.3% or
±
2
°
C, whichever is greater)
±
1 digit maximum.
Indication accuracy (see note)
Thermocouple:
(
±
0.3% of indication value or
±
1
°
C, whichever greater)
±
1 digit max.
Platinum resistance thermometer:
(
±
0.2% of indication value or
±
0.8
°
C, whichever greater)
±
1 digit max.
Analog input:
±
0.2% FS
±
1 digit max.
0.01% to 99.99% FS (in units of 0.01% FS)
0.1% to 999.9% FS (in units of 0.1% FS)
0 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
1 to 99 s (in units of 1 s)
0.0% to 100.0% (in units of 0.1%)
1,999 to 9,999 or
199.9 or 999.9 (decimal point position dependent on input type)
Temperature input:
250 ms
Current/voltage input:
100 ms
20 M
min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities
Malfunction: 10 to 55 Hz, 10 m/s
2
(approx. 1G) for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 20 m/s
2
(approx. 2G) for 2 hrs each in X, Y, and Z directions
Malfunction: 200 m/s
2
min. (approx. 20G), 3 times each in 6 directions
(100 m/s
2
(approx. 10G) applied to the relay)
Destruction: 300 m/s
2
min. (30G), 3 times each in 6 directions
Operating:
10
°
C to 55
°
C (with no icing)/3-year warranty period:
–
10
°
C to 50
°
C
Storage:
25
°
C to 65
°
C (with no icing)
Operating:
35% to 85%
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case:
IEC standard IP20
Terminals:
IEC standard IP00
Non-volatile memory (number of writings: 100,000 operations)
Approx. 170 g;
Adapter: approx. 10 g
Emission Enclosure:
EN55011 Group 1 class A
Emission AC Mains:
EN55011 Group 1 class A
Immunity ESD:
EN61000-4-2: 4 kV contact discharge (level 2)
Hysteresis
Proportional band (P)
Integral (reset) time (I)
Derivative (rate) time (D)
Control period
Manual reset value
Alarm setting range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Degree of protection
Memory protection
Weight
EMC
8 kV air discharge (level 3)
10 V/m (amplitude modulated, 80 MHz to 1 GHz)
(level 3)
10 V/m (pulse modulated, 900 MHz)
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3)
2 kV I/O signal-line (level 4)
Immunity RF-interference:
ENV50140:
Immunity Conducted Disturbance:
Immunity Burst:
ENV50141:
Approved standards
UL1092, CSA22.2 No. 142, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1)
Conforms to VDE0106/ part 100 (Finger Protection), when the separately-ordered terminal cover is
mounted.