Digital Controller
E5CK
I-81
T
C
I
How to Use the Error Display
When an error has occurred, the No.1 display alternately indicates error codes together with the current display item.
This section describes how to check error codes on the display, and the actions that must be taken to remedy the problem.
Meaning
Action
Input is in error.
Check the wiring of inputs, disconnections, and shorts, and check the input type and the input type jumper con-
nector.
For control output functions, output the manipulated variable matched to the setting of the
MV at PV error
param-
eter (level 2 mode). Alarm output functions are activated when the upper limit is exceeded.
Operation at Error
Meaning
Action
Internal memory operation is in error
First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be re-
paired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
Operation at Error
Meaning
Action
Internal circuits are in error.
First, turn the power OFF then back ON again. If the display remains the same, the E5CK Controller must be re-
paired. If the display is restored to normal, the probable cause may be external noise affecting the control system.
Check for external noise.
Control output functions turn OFF (2 mA max. at 4 to 20 mA output, and output equivalent to 0% in case of other
outputs). Alarm output functions turn OFF.
Operation at Error
This error is output only during temperature input and is displayed for two seconds when the power is turned ON.
Calibration data is in error.
Must repair.
Both control output functions and alarm output functions are active. However, note that the readout accuracy is not
assured.
Meaning
Action
Operation at Error
Meaning
Though not an error, this is displayed when the process value exceeds the display range when the control range
(setting range
±
10%) is larger than the display range (
1999 to 9999).
When less than
1999
When greater than
9999
Control continues, allowing normal operation.
Operation
Input Error
Memory Error
A/D Converter Error
Calibration Data Error
Display Range Over
相關(guān)PDF資料
PDF描述
E5AN Digital Temperature Controllers
E5AN-C3HMP-500 Digital Temperature Controllers
E5AN-C3HMTC-500 Digital Temperature Controllers
E5AN-C3MP-500 Digital Temperature Controllers
E5AN-C3MTC-500 Digital Temperature Controllers
相關(guān)代理商/技術(shù)參數(shù)
參數(shù)描述
E5CKAA1500ACDC24V 制造商:Omron Corporation 功能描述:
E5CK-AA1-500DC24 制造商:OMRON 制造商全稱:Omron Electronics LLC 功能描述:Advanced, Compact Digital Controllers
E5CK-AA1AC 制造商:OMRON 制造商全稱:Omron Electronics LLC 功能描述:Advanced, Compact Digital Controllers
E5CKAA1AC/DC24 制造商:OMRON AUTOMATION AND SAFETY 功能描述:CONTROLLER DIGITAL PROCESS 24V
E5CK-AA1-AC/DC24 功能描述:控制器 24V AC/DC BASE UNIT RoHS:否 制造商:Omron Industrial 模擬/數(shù)字:Digital 類型:Digital Temperature Controller 顯示器類型:11-Segment, 4 Digit 電源電壓:100 VAC to 240 VAC 安裝: 控制方法: 大小:48 mm x 48 mm