thinking inside the box
AC/DC CONVERTER VM - 11918
Input Voltage
85V TO 135Vrms AC 320Hz to 480Hz.
(60Hz operation permissible with additional 7300uF
100V capacitor across holdup pins)
Input Power Characteristics
MIL-STD-704E, all transient conditions excluding under
voltage surge of Figure 6.
BS2G100 and BS3G100 excluding limits 2 & 4 *
RTCA DO-160D excluding line dropouts >4ms *
* Additional external hold-up will be required.
Inrush Curret Limit
3 x steady state input current at full load and minimum
input voltage.
Output Voltages:
Output Voltage Setting
Output Current
Output Ripple
<50mV peak to peak (10MHz bandwidth)
Line Regulation 85V to 135V, 50% load
Load Regulation 115Vin, 0% to 100% Load
Output
+5
±12
+3.3
5V standby
MIN
4.95V
11.87V
3.26V
4.95V
TYP
5.05V
12.12V
3.34V
5.05V
MAX
5.15V
12.36V
3.42V
5.15V
Output
+5
±12
+3.3
5V standby
MIN
0A
MAX
30A
2.5A
10.0A
0.1A
Output
+5
±12
+3.3
5V standby
TYP
0.01%
MAX
0.1%
0.2%
0.1%
0.2%
Output
+5
±12
+3.3
5V standby
TYP
0.05%
MAX
0.2%
0.4%
0.2%
0.4%
Temperature Regulation -55°C to +85°C base plate
temperature
The units meet the following requirements of
MIL-STD-461D CE101 (Figure CE101-4), CE102,
CS101, CS114 (Curve #3),CS115, CS116 (Air
Force).
Isolation:
All outputs have separate power returns to prevent
ground loops however there is no electrical isolation
between outputs and it is intended that power
returns are linked at the load.
Grounding:
The maximum dc resistance from the chassis to the
connector earth terminal is 20 milliohms.
Efficiency:
Not less than 75% at full load, 115Vrms 400Hz
input voltage and at 25C baseplate temperature.
Output Protection:
All outputs are protected against indefinite overload
and short circuit. The outputs have cycle by cycle
current limit operating at 110-130% of full rated
current. Recovery is automatic.
Output Overvoltage Protection:
The output voltages shall not exceed the values
shown below under any circumstances. If the
voltages reach these levels the unit shall trip and
latch off. An emergency operation override is
available.
Output
+5
±12
+3.3
5V standby
TYP
±0.05%
MAX
±1.0%
Input to Output
Input to Chassis
Outputs to Chassis
>50MΩ @ 1500Vrms AC
>10MΩ @ 100V DC
Output
+5V
+12V
-12V
+3.3V
Maximum voltage
+6V
+14.5V
-14.5V
+3.9V
EMI:
Output
+5
±12
+3.3
5V standby
Transient
5% of Vout
2% of Vout
Recovery
1ms
Load Transient 50% to 100% load, 1A/us
Project2:Layout 1
10/11/09
09:45
Page 1