![](http://datasheet.mmic.net.cn/280000/FNP1000-48_datasheet_16052328/FNP1000-48_5.png)
FEB 12, 2007 revised to FEB 26, 2007
Page 5 of 13
www.power-one.com
FNP600/850/1000 AC-DC Front-Ends
& FNR-5-12/FNR-5-48 Power Shelves Data Sheet
Safety, Regulatory, and EMI Specifications
Parameter
Conditions/Description
Min.
Nom.
Max.
Units
Agency Approvals
UL60950, (UL) CSA 60950 (cUL), EN60950 (TüV), CE Mark for LVD.
Electromagnetic
Interference
FCC CFR title 47 Part 15
Sub-Part B,
EN55022/CISPR 22.
Conducted:
Radiated:
B
A
Class
Harmonics
Per IEC61000-3-2.
A
Class
Voltage Fluctuation
and Flicker
Per IEC61000-3-3.
Pass
ESD Susceptability
Per EN61000-4-2, Level 4.
8
.
kV
Radiated
Susceptability
Per EN 61000-4-3, Level 3.
10
.
V/M
EFT/Burst
Per EN 61000-4-4, Level 4.
±
4
.
kV
Input Transient
Protection
Per EN 61000-4-5, Class 3.
Line-to-Line:
Line-to-Ground:
1
2
.
kV
RF Conducted
Disturbances
Per EN 61000-4-6, Level 3.
10
.
V
Voltage Interruptions
Per EN 61000-4-11, performance criterion B 30%.
Per EN 61000-4-11, performance criterion C 60%.
Per EN 61000-4-11, performance criterion C 95%.
10
100
5
.
ms
ms
Sec
Voltage Sag Immunity
Per SEMI F47-0999 > 100 VAC.
No output voltage interruption.
.
Leakage Current
Per EN60950.
At 240 VAC:
3.5
mA
Environmental Specifications
Parameter
Conditions/Description
Min.
Nom.
Max.
Units
Altitude
Operating.
Non-Operating.
10K
40K
ASL ft
ASL ft
FNP600-12:
FNP850-12:
FNP600-48:
FNP1000-48:
Internal DC fan for cooling. At 100% load:
At 50% load:
0
0
50
70
oC
Operating Temperature
FNP850-12R:
Internal DC fan for cooling. At 100% load:
At 94% load:
At 50% load:
0
0
0
40
50
70
oC
Storage Temperature
-40
85
oC
Temperature Coefficient
0 oC to 70 oC (after 15-minute warm-up).
0.02
%/oC
Relative Humidity
Non-condensing
95
%RH
Shock
Operating: half-sine, 10 ms, 3-axis.
Non-Operating: half-sine, 10 ms, 3-axis.
+20
+40
Gpk
Gpk
Vibration
Operating: swept sine 5-2000-5 Hz, 5-32
Hz, 0.02DA, 32-2000 Hz.
Non-operating: random 10-2000 Hz.
1
6.15
Gpk
Grms
Reliability
Parameter
Conditions/Description
(Calculated) MILHDBK 217F Ground Benign.
Demonstrated.
Useful Life.
Min.
100 000
250 000
10
Nom.
Max.
Units
hrs
hrs
yrs
MTBF