FNP1500/1800 and FXP1500/1800 Front-Ends
& FNR-3 and FXR-3 Power Shelves Data Sheet
Safety Specifications
Maximum electric strength testing is performed in the factory according to EN 550116, IEC/EN 60950, and UL 60950.
Input-to-output electric strength tests should not be repeated in the field. Power-One will not honor any warranty claims resulting
from electric strength field tests.
Parameter
Conditions/description
Min
Nom
Max
Unit
Agency approvals
UL60950, (UL) CSA 60950 (cUL),
EN 60950(TüV), CE Mark for LVD
Insulation safety rating
Input to case
Input to output
Output to case
Basic
Reinforced
Functional
Electric strength test voltage
Input to case
Input to output
Output to case
Output 1 to output 2
2.12
4.2
1
0.5
0.1
kVDC
kVDC
kVDC
kVDC
1
Subassemblies are pre-tested with 4.2 kVDC in accordance with EN50116 and IEC/EN60950.
EMC Specifications
Parameter
Description
Criterion
Electrostatic discharge
Electromagnetic field
Electrical fast transients/burst
Surge
Voltage dips and interruptions
RF conducted immunity
IEC/EN 61000-4-2, level 4
IEC/EN 61000-4-3, level 3
IEC/EN 61000-4-4, level 3
IEC/EN 61000-4-5, level 3
IEC/EN 61000-4-11
IEC/EN 61000-4-6
Performance criterion B
Performance criterion A
Performance criterion B
Performance criterion B
Performance criterion B or better
10 VAC, AM 80 %, 1 kHz
Performance criterion A
Class B
Class A
Class B
Pass
Pass
Emissions conducted
Emissions radiated
Harmonics
Voltage fluctuation and flicker
Voltage sag
CISPR 22/EN 55022/EN 61204
CISPR 22/EN 55022/EN 61204
IEC/EN 61000-3-2
IEC/EN 61000-3-3
SEMI F47-0200 (High Line 230V)
Input Specifications
Specification is valid for input voltage, load, and temperature ranges, unless otherwise stated.
Parameter
Conditions/description
Min
Nom
Max
Unit
Input voltage
85
230
264
VAC
Input frequency
47
50/60
63
Hz
Turn-on input voltage
Ramping up
79
-
85
VAC
Turn-off input voltage
Ramping down
70
-
78
VAC
Inrush current limitation
115/230 VAC acc. ETS 300 132-1
< 100 ms
After last AC line peak ,
V
i
= 230 VAC,
P
o nom
V
i nom
,
I
o nom
V
i
= 230 VAC,
I
o nom
,
T
C
= 25 °C
50
A
pk
ms
Hold-up time
20
Power factor
0.95
89
1
W/VA
Efficiency
90
%
Max input current
20
A
rms
Input connector
16A – 20 A / 250 VAC; according to IEC320 C19
1
87% for FNP1500-12
Input Connector Description (FXP1500/1800)
Protection Earth
P1
PE
Phase
Neutral
P2
P3
L
N