2
Specifications are subject to change without notice (26.07.05)
FAA01, FAA08
Function and Time Setting
Range and operation mode selection
Operating mode display window
Operating mode selector
(function A, B
2
, E, J)
Scale range display windows
Time unit selector (sec, min, hrs, 10h)
Time setting knob (set time)
Power indicator (green)
(Flashes when timer operates;
on when timer stops operating)
Time range selector
(1.2, 3, 12 and 30 at full scale)
Output indicator (red)
(Lit when output is ON)
Time unit display window
Mode of Operation
Function A
Delay on operate
The set delay period begins
as soon as the power supply
is connected. At the end of
the set delay the relay oper-
ates and doesn’t release
until the power supply is
interrupted for at least 100
ms.
Function B
Symmetrical recycler
(ON first)
The relay operates and the
time period start as soon as
the power is applied. At the
end of the first set time peri-
od, the relay releases. At the
end of the second time peri-
od (equal to the first), the
relay operates again. This
sequence continues with
equal ON- and OFF- time
periods until the power sup-
ply is interrupted for at least
100 ms.
Function E
Interval
The relay operates and the
time period begins as soon
as the power is applied. The
relay releases at the end of
the time period or when the
power supply is disconnect-
ed for at least 100 ms.
Function J
One shot
The time period begins as
soon as the power supply is
connected and at the end of
this period the relay operates
for 1s.
Indication for
Power supply On
LED, green
(flashing when timing)
LED, red
Output ON
Environment
Degree of protection
Operating temperature
Ambient humidity
Housing dimesions
Weight
CE marking
EMC
Immunity
Emission
IP 40
-10 to +55 °C (14 to 131 °F)
35 to 85% RH
48 x 48 mm
Approx. 95 g
Yes
Electromagnetic Compatibillity
According to EN 61000-6-1
According to EN 61000-6-3
(front panel)
General Specifications
Upper right knob:
Setting of function
A
- delay on operate
B
2
- simmetrical recycler
E
- interval
J
- one shot
Lower right knob:
Time unit selector
sec
(seconds)
min
(minuts)
hrs
(hours)
10h
(10 hours)
Lower left knob:
Time range selector
1.2
,
3
,
12
and
30
Centre knob:
Time setting on relative
scale