11
Approvals
Three Phase Filters
F.LL.D3 series – HN.R2 type
Industrial environments
High performance, high voltage, general applications
Offered as an extension to the standard AN/HN.*1 series, these products
are rated at 600Vac, whilst still maintaining performance characteristics
required for industrial frequency inverter and motor drive applications.
Current ratings from 8A to 450A
High voltage design - 600Vac
High attenuation performance
Safety terminal blocks for easy installation
3 phase + neutral designs available
Filter range
Code
IR
IL
Cx
Cy
L
R
LR
Circ
(A)
(mA)
(F)
(nF)
(mH)
(M)
(m)
diag
F.LL.D3.008A.HN.R2
8
24
3x2.2 + 3x1.0
3x10 + 3x47
3x7.6
3 x 1
< 38
A
F.LL.D3.016A.HN.R2
16
24
3x4.4 + 3x2.2
3x10 + 3x47
3x5.2
3 x 1
< 10
A
F.LL.D3.025A.HN.R2
25
275
3x4.4 + 3x4.4
3x10 + 2x1 F + 3x94
3x2.2
6 x 1.5 + 2 x 0.68
< 4.3
B
F.LL.D3.036A.HN.R2
36
275
3x4.4 + 3x4.4
3x10 + 2x1 F + 3x94
3x1.3
6 x 1.5 + 2 x 0.68
< 2.4
B
F.LL.D3.050A.HN.R2
50
275
3x4.4 + 3x4.4
3x10 + 2x1 F + 3x94
3x0.8
6 x 1.5 + 2 x 0.68
< 1.5
B
F.LL.D3.080A.HN.R2
80
315
3x6.7 + 3x6.7
3x94 + 2x1 F + 3x94
3x0.9
6 x 1.5 + 2 x 0.68
< 1.2
B
F.LL.D3.110A.HN.R2
110
315
3x6.7 + 3x6.7
3x94 + 2x1 F + 3x94
3x0.5
6 x 1.5 + 2 x 0.68
< 0.7
B
F.LL.D3.180A.HN.R2
180
335
3x5 + 3x5
3x94 + 2x1 F + 3x94
3x0.5
6 x 1.5 + 2 x 0.68
< 0.5
B
F.LL.D3.280A.HN.R2
280
470
3x10 + 3x10
3x282 + 2x1 F + 3x282
3x0.31
6 x 1.5 + 2 x 0.68
< 0.3
B
F.LL.D3.450A.HN.R2*
450
470
3x10 + 3x10
3x282 + 2x1 F + 3x282
3x0.075
6 x 1.5 + 2 x 0.68
< 0.25
B
Electrical specifications
Rated voltage (VR):
600Vac, 50/60Hz at 40°C
Rated current (IR):
referred to room temperature = 40°C
Leakage current (IL):
at 440V / √3, 50Hz, max value
Voltage test (2S):
line to ground 3470Vdc
line to line 1700Vdc
Climatic category:
HPF (25/085/21);
temperature range: -25°C to +85°C
Mechanical specifications
Manufacture: metal enclosure, electrical components
sealed with self-extinguishing resin.
Connections: Phases: terminal blocks – all current ratings.
Earth: threaded with nuts plus washer:
8A to 50A = M6; 80A to 280A = M10; 450A = M16
Circuit diagram A
Circuit diagram B
Line
Load
Line
Load
Except model marked*
= See leakage current note on page two