I-6
Temperature Controller
E5C2
Specifications
I
Ratings
Note:
Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.
I
Input Ranges
Note: 1.
Values in ( ) are the minimum unit.
2.
Values in ( ) are the thermistor resistive value.
I
Characteristics
Note: 1.
No reset function is incorporated by any E5C2 model with ON/OFF control.
2.
The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.
Supply voltage
100/110/120 VAC (common), 200/220/240 VAC (common) (See note.)
50/60 Hz (common)
90% to 110% of rated supply voltage
Approx. 2 VA
Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor
ON/OFF or P control
Analog setting
No indication
Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)
Operating voltage range
Power consumption
Input
Control mode
Setting method
Indication method
Control output
Input
Thermocouple
Platinum resistance
thermometer
Pt100
Thermistor (see note 2)
K (CA)
Chromel vs. alumel
0 to 200 (5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)
32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)
J (IC)
Iron vs. constantan
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
THE
Range
°
C
–
50 to 50 (2),
–
20 to 80 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)
32 to 212 (5),
32 to 392 (10)
–
50 to 50 (2) (6 k
at 0
°
C),
0 to 100 (2) (6 k
at 0
°
C),
50 to 150 (2) (30 k
at 0
°
C),
100 to 200 (2) (550
at 200
°
C),
150 to 300 (2) (4 k
at 200
°
C)
°
F
32 to 392 (10),
32 to 572 (20),
32 to 752 (20)
---
Setting accuracy
Hysteresis
Proportional band
Control period
Reset range (see note 1)
Insulation resistance
Dielectric strength
Vibration resistance
±
2% FS max.
Approx. 0.5% FS (fixed)
3% FS (fixed)
Approx. 20 s
5
±
1% FS min.
20 M
min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts
Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions
Malfunction: 147 m/s
2
, 3 times each in 6 directions
Destruction: 294 m/s
2
, 3 times each in 6 directions
Electrical:
100,000 operations min. (3 A at 110 VAC, resistive load)
Operating:
–
10
°
C to 55
°
C (with no icing or condensation)
Operating: 45% to 85%
Front panel: IEC standard IP40 (see note 2)
Terminals:
IEC standard IP00
Approx. 200 g (with flush-mounting adapter)
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Degree of protection
Weight