  • 參數(shù)資料
    型號(hào): CCL450DE1-AD
    廠商: Electronic Theatre Controls, Inc.
    英文描述: 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    中文描述: 6日和12伏,75至450瓦特濕電池鉛鈣電池
    文件頁數(shù): 2/2頁
    文件大?。?/td> 126K
    代理商: CCL450DE1-AD
    Housing
    18 gauge steel housing with a tan epoxy powder coat
    finish.
    Knockouts provided for mounting up to three lamp
    heads.
    The suggested lamp head is the “D” Series round
    sealed beam Par 36 tungsten. To order lamp heads
    other than the suggested “D” head, refer to Chloride
    Accessories Section..
    Self-Diagnostics
    The ACCU-TEST Self-Diagnostics option conducts
    automatic and manual tests, and indicates real time
    status of the lamp, battery and charger via LED indica-
    tor lamps. Automatic tests include: Systems analysis
    every 10 seconds, with actual load tests performed for
    a 3 minute duration every 30 days. A manual tests is
    available from 1 to 90 minutes.
    Battery
    Low maintenance, free electrolyte, wet cell, lead calci-
    um battery.
    Standard sustained emergency operation is for 90
    minutes with the illumination source providing full
    light output.
    The suggested operating temperature range for lead
    calcium batteries is 65°F
    (19°C)
    to 85°F
    (30°C)
    and
    should provide a service life of 5 years.
    Performance
    Input power requirements
    120 VAC - 0.66 amps, 80 watts
    277 VAC - 0.30 amps, 80 watts
    Code Compliance
    The CCL/TCL Series meets or exceeds all performance
    standards as required by UL 924, NFPA 70, NFPA 101,
    NEC and OSHA.
    Specification Data for CCL/TCL Series Steel Emergency Lighting Units
    Suggested Specification
    Furnish and install Chloride Systems emergency lighting unit model ________. The unit shall be constructed to meet Underwriter’s Laboratories, Inc. Standard #924
    and the National Electrical Code (NEC).
    INSTALLATION AND OPERATION -
    Unit shall be easily field connected to a 120 or 277 VAC, 60 hertz, unswitched power source. Installation must comply with the
    NEC as well as other applicable codes. Upon utility power failure or brownout, the unit shall automatically transfer to battery power and maintain the required illumina-
    tion level for a minimum period of 90 minutes. Upon restoration of utility power, the charger shall restore the battery to full charge within UL 924 requirements follow-
    ing a rated discharge of not more than 90 minutes.
    CHARGER -
    Product shall utilize a fully automatic, voltage regulated, two-rate current limited solid-state charger. The charging system shall maintain the battery at
    full capacity without the need for periodic exercising or equalization. The following features shall be standard: Low voltage disconnect (LVD), brownout protection and
    AC lockout.
    BATTERY -
    The battery shall be a low maintenance, free electrolyte, wet cell, lead calcium battery. The lead calcium battery shall provide trouble-free operation in
    temperatures up to 85°F (30°C).
    HOUSING -
    The unit housing shall be constructed of 18 gauge steel with a tan epoxy powder coat finish.
    Chloride Systems
    ISO 9001
    A2528
    C1063
    R4
    9/02 IH
    272 West Stag Park Service Road
    Burgaw NC 28425
    Telephone: (910) 259 1000
    Facsimile: (800) 258 8803
    www.chloridesys.com
    Lamp Head Photometrics
    (For DL, suggested head for CCL)
    Horizontal
    Left 30
    (For DK, suggested head for TCL)
    Operation
    DC
    Suggested
    Lamp Head
    Watts to 87
    1
    of Rated Voltage*
    2 hrs. 4 hrs. 8 hrs.
    56
    28.5
    75
    112.5
    169
    85.5
    112.5
    150
    225
    337.5
    Voltage
    Unit
    1
    1
    2
    hrs.
    75
    100
    150
    225
    150
    200
    300
    450
    6
    CCL75
    CCL100
    CCL150
    CCL225
    TCL150
    TCL200
    TCL300
    TCL450
    DL
    DL
    DL
    DL
    DK
    DK
    DK
    DK
    15
    20
    30
    45
    30
    34
    60
    90
    38
    57
    12
    57
    96
    114
    171
    Electronics
    120/277 VAC dual voltage input with surge-protect-
    ed, solid-state charging circuitry provides for a
    reliable charging system. The charging system is
    furnished with low voltage disconnect, AC lockout,
    brownout protection, AC indicator lamp and test
    switch.
    The low voltage disconnect (LVD) feature will dis-
    connect the battery prior to an unacceptable deep
    discharge, but not before the required 90 minute
    emergency operation.
    The AC lockout feature prevents battery drain prior to
    the initial energizing of utility power, and allows the
    installer to complete all wiring and electrical connec-
    tions without energizing the emergency circuit.
    The brownout protection circuitry will automatically
    switch the unit into the emergency mode if the utility
    voltage sags below 20% of nominal.
    Battery charging circuitry is entirely solid-state, and
    utilizes a fully automatic, voltage regulated charger.
    Battery recharge time after full discharge is less than
    the required UL 924 standard.
    Line sensitive electronics cause an instantaneous
    transfer to battery power if utility power is lost, or a
    brownout condition is detected. When line voltage is
    present and stabilized, the transfer circuitry switches
    back to normal operation and begins recharging the
    battery. The transfer circuitry can be tested via a
    momentary test switch located on the housing.
    Vertical
    20
    30
    50
    10
    0
    Up 20
    10
    feet 0
    10
    Down 20
    .2
    .1
    40
    60
    70
    .3
    1
    .5
    Horizontal
    20
    30
    50
    10
    0
    Left 20
    10
    feet 0
    10
    Right 20
    .2
    .1
    40
    60
    70
    .3
    1
    .5
    20
    30
    50
    10
    0
    Up 20
    10
    feet 0
    10
    Down 20
    Photometric No. 3
    40
    60
    70
    80
    1
    .3
    .2
    .1
    .5
    20
    30
    50
    10
    0
    10
    feet 0
    10
    20
    Right 30
    1
    .3
    .2
    .1
    20
    .5
    40
    60
    70
    80
    相關(guān)PDF資料
    PDF描述
    CCL450DE1-ADAL 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-ADTD 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-DCP 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-EX 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-TD1 6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    相關(guān)代理商/技術(shù)參數(shù)
    參數(shù)描述
    CCL450DE1-ADAL 制造商:未知廠家 制造商全稱:未知廠家 功能描述:6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-ADTD 制造商:未知廠家 制造商全稱:未知廠家 功能描述:6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-DCP 制造商:未知廠家 制造商全稱:未知廠家 功能描述:6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-EX 制造商:未知廠家 制造商全稱:未知廠家 功能描述:6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery
    CCL450DE1-TD1 制造商:未知廠家 制造商全稱:未知廠家 功能描述:6 and 12 Volt, 75 to 450 Watts Wet Cell Lead Calcium Battery