6B11 / 6B11HV
Models 6B11 and 6B11HV
Rev. 0 | Page 3 of 8
Range Description
(Software Configurable)
Accuracy
1
(Typical)
Accuracy
1
(Maximum)
Noise
(Peak-to-Peak)
±15 mV
±0.03 % FS
±0.06 % FS
±0.02 % FS
±50 mV
±0.015 % FS
±0.04 % FS
±0.01 % FS
±100 mV
±0.0055 % FS
±0.03 % FS
±0.005 % FS
±500 mV
±0.005 % FS
±0.03 % FS
±0.002 % FS
±1 V
±0.005 % FS
±0.03 % FS
±0.005 % FS
±5 V
±0.005 % FS
±0.03 % FS
±0.0015 % FS
±20 mA
±0.008 % FS
2
±0.03 % FS
2
±0.005 % FS
J Thermocouple, 0°C to 760°C
±0.4°C
±0.75°C
±0.14°C
K Thermocouple, 0°C to 1000°C
±0.5°C
±0.75°C
±0.22°C
T Thermocouple, -100°C to +400°C
±0.5°C
±0.75°C
±0.2°C
E Thermocouple, 0°C to +1000°C
±0.5°C
±0.75°C
±0.2°C
R Thermocouple, +500°C to +1750°C
±0.63°C
±1.5°C
±0.3°C
S Thermocouple, +500°C to +1750°C
±0.62°C
±1.5°C
±0.4°C
B Thermocouple, +500°C to +1800°C
±1.2°C
±2.0°C
±0.7°C
1
Accuracy is given for 6B11 and 6B11HV module only. When measuring thermocouple signals, the CJC temperature sensor error should
be added to the module accuracy to compute the system accuracy. The AC1361 CJC temperature sensor is provided on each channel of
the 6B Series backplanes.
2
Does not include the error of the current to voltage input resistor, Model AC1381.
6B11 and 6B11HV Specifications
(typical @ +25°C and V
s
= +5 V dc)
Description
Model 6B11 and 6B11HV
Inputs, Software Selectable
Thermocouple Types
J, K, T, E, R, S, B
mV
±15 mV to ±500 mV (Refer to Model Table)
Volt
±1 V; ±5 V
Current Range
±20 mA
Communications
Protocol
RS-485
Baud Rates, Software Selectable
300K, 600K, 1.2K, 2.4K. 9.6K, 19.2K
Accuracy
Initial @ +25°C
Refer to Model Table
Input Offset vs. Temperature
±0.3
μ
V/°C
Span vs. Temperature
±3 ppm/°C (±25 ppm/°C, maximum)
Cold Junction Compensation
1
Initial Accuracy @ +25°C
±0.25°C (±0.75°C, maximum)
Accuracy, +5°C to +45°C
±0.5°C (±0.0125°C/°C)