258
Technical data
VAA-4EA-G4-ZE/E2
Function
C
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group Tel.: Germany (06 21) 7 76-0 USA (330) 4 25 35 55 Singapore 7 79 90 91 Internet http://www.pepperl-fuchs.com
Copyright Pepperl+Fuchs, Printed in Germany
D
2
The VAA-4EA-G4-ZE/E2 is an AS-Interface
coupling module with four inputs and four out-
puts. Mechanical contacts and 2- and 3-wire
sensors can be connected to the inputs. The
sensors are supplied via the module. The out-
puts are electronic outputs, which can be loa-
ded to 24 V DC and 2 A per output (total load <
4 A).
The IP67 rated G4-PG module is especially
suitable for rough conditions. Sensors and ac-
tuators attach to PG cable glands and cage
tension spring terminals thus making the instal-
lation especially user-friendly. For pre-addres-
sing the module it can be plugged directly onto
the adapter of the hand-held programming de-
vice VBP-HH1.
The current switching state of each channel is
indicated by an LED, located on the module's
top side. In the case of communication errors
on the bus, the outputs are de-energised via an
integrated watchdog, which can be deactivated
by the parameter bit P0.
Both flat and round cables can be used for the
AS-i transmission line and the external
24 V DC power supply. Use the U-G1FF base
for the AS-i flat cable. The AS-Interface stan-
dardised EEMS interface, uses the cable pier-
cing method to connect both the yellow and
black flat cables.
Use the U-G1PP base for the round cable. The
AS-i-cable as well as the external power supply
may be connected within this base.
General specifications
Slave type
Indicators/operating means
LED AS-i
Standard slave
dual LED green/red
green: AS-i voltage
red: communication error or address 0
green/red flashing: overload sensor supply
ext. auxiliary voltage U
AUX
; LED green
switching state (input); 4 LED yellow
switching state (output); 4 LED yellow
LED AUX
LED IN
LED OUT
Electrical specifications
Auxiliary voltage U
AUX
24 V DC
±
15 % PELV
(protection class 3 in accordance with VDE
0106/IEC 364-4-41)
26.5 ... 31.6 V from AS-Interface
£
60 mA (without sensors)
Rated operational voltage U
e
Rated operational current I
e
Input
Number/Type
Supply
Current loading capacity
4 inputs for 2- or 3-wire sensors (PNP), DC
from AS-Interface
£
180 mA (T
B
£
40 °C),
£
140 mA (T
B
£
60 °C), short-circuit-proof
OFF
£
1.5 mA
ON
4.5 mA
Switching point
Output
Number/Type
Voltage
Current
Ambient conditions
Ambient temperature
Storage temperature
Mechanical specifications
Protection degree
Connection type
4 electronic outputs, PNP
ext. auxiliary voltage U
AUX
- 0.5 V
2 A per output, 4 A total
-25 ... 60 °C (248 ... 333 K)
-25 ... 85 °C (248 ... 358 K)
IP67 according to EN 60529
cable piercing method or terminal compartment
flat cable yellow/flat cable black or standard
round cable
inputs/outputs: PG7 screwed connection and
cage clamp terminals
350 g
top hat section rail or screw mounting
Mass
Mounting
Programming instructions
Profile
IO code
ID code
Programming instructions
(bit configura-
tion)
Data bits
(function via AS-Interface)
D0
D1
D2
D3
Parameter bits
(programmable via AS-i)
S-7.F
7
F
input output
IN1
IN2
IN3
IN4
function
communication monitoring
P0 = 1 (basic setting), monitoring = ON, i.e. if
communication fails, the outputs are de-ener-
gised
P0 = 0, monitoring = OFF, if communication
fails, the outputs maintain their condition
not used
not used
not used
OUT1
OUT2
OUT3
OUT4
P0
P1
P2
P3
Matching system
components
U-G1FF
Base for connection to flat cable (EEMS;
AS-i and external auxiliary voltage)
U-G1FFA
Base with addressing jack for connection to flat
cable (EEMS; AS-i and external auxiliary volta-
ge)
U-G1PP
Base for connection to round cable (EEMS;
AS-i and external auxiliary voltage)
Accessories
VAZ-G4-B
Blind plug PG7
VBP-HH1
Hand-held programming device