Specifications
16, 25, 36,
Maximum leakage current, each
6 Amps
50 Amps
line-to-ground @ 120 VAC 60 Hz:
2.9mA
5.7 mA
@ 250 VAC 50 Hz:
4.9mA
9.8 mA
Hipot rating (one minute):
line-to-ground
2250 VDC
line-to-line
1450 VDC
Operating frequency:
50/60 Hz
Rated voltage:
440 VAC phase-to-phase
250 VAC phase-to-neutral/ground
Rated current:
@ 440 VAC phase-to-phase
6FCD
6 Amps
16FCD
16 Amps
25FCD
25 Amps
36FCD
36 Amps
50FCD
50 Amps
Typical insertion loss in dB:
Line-to-ground in 50 ohm circuit
Current
Frequency–MHz
Rating
.01 .03 .05
.1
.5
1
5
10
30
6A
2
14
23
39
56
52
48
45
33
16A
13
30
36
45
75
52
45
35
25A
13
30
36
45
75
52
45
35
36A
9
26
32
40
75
52
45
35
50A
9
26
32
40
75
52
45
35
Line-to-line in 50 ohm circuit
Current
Frequency–MHz
Rating
.01 .03 .05
.1
.5
1
5
10
30
6A
9
8
24
40
62
57
50
48
38
16A
9
13
24
55
75
65
60
25A
9
13
26
55
75
65
60
36A
9
13
26
46
75
65
60
50A
9
13
26
46
75
65
60
40
Libertyville, IL (847) 680-7400
CD
40
FCD Series
Three Phase External
Power Line Filter
for Frequency Converters
FCD Series
The FCD filters provide three phase filtering for frequency
inverters and variable speed motor drives. Designed for
very noisy Delta applications, they attenuate conducted
interference at low and high frequency ranges and
protect programmable logic controllers from RF noise on
the AC power line. These filters perform best when
installed on the line side of the motor drive. The FCD
filters prevent noise from returning to the line, enabling
equipment to meet strict European regulations on RFI.
Suited for field wiring applications, these filters are ideal
for EMC troubleshooting and field refurbishing. The FCD
filters feature side flanges for easy mounting and DIN
type terminals which eliminate live metal parts, allowing
safe and easy connection. They could also be sold as an
accessory to motor drives marketed into Europe.
Electrical Schematics
6 Amp
16, 25, 36 & 50 Amps
Resistor location for reference only.
FCD10
UL Recognized